DC Panel

Category
Item Description
Emergency discharge capability Shall provide continuous discharge during a power failure condition. The emergency duration is selected as 1 hour.
Remaining capacity before discharge end The remaining capacity at the end of discharge, just before closing, shall not be less than 25% of the rated capacity.
DC bus voltage dip Shall ensure that the DC bus voltage drop does not exceed 10% when a surge load occurs.
Closing current for maintenance-free batteries Generally shall not exceed 4C.
Reserve factor (aging allowance) A reserve factor of 1.2 is adopted to account for capacity degradation of the battery bank at the end of its service life.
Capacity design reference Specific capacity design shall refer to applicable national standards and technical documentation provided by the battery manufacturer.

Product detail:

Item Description
Cabinet One unit (including charging and feeder sections), 800×600×2260 mm, color RAL7035
Output Circuits 5 control circuits (10A), 5 closing / trip circuits (20A)
Charging Module 5A × 2 units
Monitoring Module 1 unit
Integrated Measurement Module 1 unit (including insulation monitoring and battery inspection)
Battery 40AH × 18 blocks
AC Input Supports dual 380V AC inputs (with automatic transfer)