The DL series power-special UPS,they are professionally designed for power plants, substations and distribution stations, featuring double-conversion online mode and zero switching function.
They are mainly applied to power telecontrol, RTU, power carrier communication, power monitoring and other power system scenarios.
Product Specifications
| Model | DL5K | DL10K | DL15K | DL20K | DL30K | DL40K | DL50K | DL60K | DL80K |
|---|---|---|---|---|---|---|---|---|---|
| Rated Capacity | 5KVA | 10KVA | 15KVA | 20KVA | 30KVA | 40KVA | 50KVA | 60KVA | 80KVA |
AC Input
| Parameter | Specification |
|---|---|
| Phases | Single / Three-Phase + N + G |
| Nominal Voltage | 220/380VAC ± 20% |
| Nominal Frequency | 50/60Hz ± 10% |
| Power Factor | 0.8, 0.95 (with input filter or 12-pulse rectifier) |
| Soft Start | 0~100% in 5s |
Bypass Input
| Parameter | Specification |
|---|---|
| Phases | Single / Three-Phase + N + G |
| Nominal Voltage | 220/380VAC ± 15% |
| Nominal Frequency | 50/60Hz ± 5% |
DC System
| Parameter | Specification | ||||||||
|---|---|---|---|---|---|---|---|---|---|
| Nominal DC Voltage | 220V | ||||||||
| Cut-off Voltage | 185V | ||||||||
| Max. Discharge Current | 22A |
AC Output
| Parameter | Specification |
|---|---|
| Phases | Single / Three-Phase + N + G |
| Nominal Voltage | 220V ± 1% (steady load), 220V ± 3% (load fluctuation) |
| Nominal Frequency | 50/60Hz ± 0.05 (battery mode) |
| Power Factor | ≥0.8 |
| Output Waveform | Sine wave |
| Total Harmonic Distortion (THD) | Linear load <3%, Nonlinear load <5% |
| Dynamic Load Voltage Transient Range | ±5% (0~100% load step) |
| Recovery Time | <10ms |
| Crest Factor | 3:1 |
Overload Capability
| Parameter | Specification |
|---|---|
| Overload Capability | 125% for 10 min, 150% for 1 min, >150% for 200ms |
Protection Functions
| Parameter | Specification |
|---|---|
| Protection Functions | Overvoltage, undervoltage, overcurrent, short circuit, overtemperature, etc. |
| Efficiency | >91%, >95% (ECO mode) |
Communication Interfaces
| Parameter | Specification |
|---|---|
| Communication Interfaces | RS232 / RS485 / RS422 / SNMP |
Operating Environment
| Parameter | Specification |
|---|---|
| Operating Temperature | 0°C ~ 40°C |
| Relative Humidity | 10% ~ 90% (non-condensing) |
| Altitude | <2000m (Capacity derates by 1% per 100m elevation gain) |
| Cooling Method | Forced air cooling |
Dimensions (WxDxH) mm
| Parameter | Specification | ||||||||
|---|---|---|---|---|---|---|---|---|---|
| Dimensions (WxDxH) mm | 800x600x2260 / 800x800x2260 | ||||||||
| Weight (kg) | 210 |
Options
| Parameter | Specification |
|---|---|
| Options | RS485 / SNMP network adapter / harmonic compensation cabinet / input/output distribution cabinet / input/output isolation cabinet / lightning protection device / bypass voltage regulator cabinet / custom cabinet dimensions available upon request |
We will contact you within 1 working day, please pay attention to the email with the suffix “@wardelectricalsolution.com”.